Construction ID: SSR-U

Carpet / tiles / timber / laminates / synthetics

Sand / cement or liquid anhydrite screed

System Standard

UDL

2.0 kN/m²

Liquid screed | sand / cement screed

Construction height

35mm

16mm self adhesive clip rails

Jupiter 16mm multi layer pipe

Jupiter System Standard ROK

Perimeter mineral wool perimeter insulation

Moisture barrier (if required)

Sealing strip

85-95*

Technical Data

Construction suitable for upper floor constructions

Construction height

mm

85-95*

Height excluding floor finish

Mass

kg/m²

110-140

Mass excluding floor finish

Thermal resistance, R-value

m²K/W

0.86

Uniform Distributed Load (UDL)

Point load (≥ 20cm²)

Impact sound reduction

Area of application

Floors with rooms of equal

temperature above & below

Rmin=0.75 m²K/W

Additional information

kN/m²

2.0

kN

1.0

dB

≥28

This construction is suitable intermediate floor constructions. No further insulation is required to meet Part L requirements.

 

For ground floor construction see construction SSR-G

Services can such as flow and return pipes etc can be run within primary insulation and back filled with loose fill levelling compound..

 

  • 85mm includes 55mm liquid screed on 30mm insulation. (35mm min. coverage over pipework.

  • 95mm includes min. 65mm sand cement screed 30mm insulation. (45mm min. coverage over pipework.

  • For additional load i.e. 3 kN/m² increase by further 15mm anhydrite or 20mm sand /cement.

Strict heating up protocol applies with all ‘in’ screed systems.

Valid on concrete floors >12cm (DIN EN 4109: m² > 276kg/m²)